• 叠加式算力单元

Stacked Computing Unit

Maintain vertical alignment (±1 degree) during installation. Operating environment: Temperature-20°C to 45°C, humidity ≤90% RH. Caution: Condensation may occur in low temperatures. For installations above 2,000 meters altitude, transformers and switches require capacity reduction (approximately 1% per 100-meter elevation). Product operating temperature does not reflect server environment. This containerized data center includes three-phase distribution cabinets, power sockets, network equipment, server racks, and exhaust fans. Additional technical support is available upon request.
  • Product Description
  • Product Specifications

Important Notes:

  • Maintain vertical alignment (±1 degree) during installation.
  • Operating environment: Temperature-20°C to 45°C, humidity ≤90% RH. Caution: Condensation may occur in low temperatures.
  • For installations above 2,000 meters altitude, transformers and switches require capacity reduction (approximately 1% per 100-meter elevation).
  • Product operating temperature does not reflect server environment.
  • This containerized data center includes three-phase distribution cabinets, power sockets, network equipment, server racks, and exhaust fans. Additional technical support is available upon request.
SubsystemProjectParameterRemark
Power Supply and DistributionIT total load1200kW
Power density per cabinet≤200kW
Power Supply StandardThree‑phase four‑wire + PE, 380V / 400V / 415V AC, 50Hz/60Hz
Power Distribution Unit (PDU)400A*6The intelligent PDU is optional.
battery capacity1200kVA/1200kW
Battery standby time15 min
CabinetIT cabinet capacity6 X 42U IT cabinet
Cabinet dimensions (width x depth x height mm)600mm X 1100mm X 2000mm
Temperature controlNet cooling capacity15 kW per unit (1+1 redundancy)
FanAC fan
Temperature control range18~27 ℃
Cold and Hot ChannelsClosed thermal channel
Fire fightingAutomatic Fire Extinguishing SystemA gas fire suppression system equipped with automatic temperature control, flue gas detection devices, and emergency release functionality
AlarmThe monitoring system supports audio and visual alarms.
fire extinguishing gasHeptafluoropropane
Early DetectionSupport VESTA
MonitorBox door access controlStandard ID card access controlThe IC card payment system is optional.
Cabinet access controlStandard mechanical door lockThe smart door lock is customizable.
Monitoring and ManagementInternal temperature and humidity real‑time monitoring and control system, access control system, fire detection and control system
Proximal display within the moduleRemote access to the customer monitoring system display
Mobile Operations and Maintenancephone APPThe optional SMS Cat only supports remote display via the app; it does not support control.
Prefabricated Module StructureExternal dimensions (length x width x height, mm)13716mm×3500mm×3500mm+12192mm×2438mm×2896mm
Insulation layer thickness50mm rock wool board
Maintenance channel dimensionsCold channel width: ≥1000 mm  Hot channel width: ≥800 mm