Modular Computing Power Unit

Maintain vertical alignment (±1 degree) during installation. Operating environment: Temperature-20°C to 45°C, humidity ≤90% RH. Caution: Condensation may occur in low temperatures.For installations above 2,000 meters altitude, transformers and switches require capacity reduction (approximately 1% per 100-meter elevation). Product operating temperature does not reflect server environment.
  • Product Description
  • Product Specifications

Important Notes:

  • Maintain vertical alignment (±1 degree) during installation.
  • Operating environment: Temperature-20°C to 45°C, humidity ≤90% RH. Caution: Condensation may occur in low temperatures.
  • For installations above 2,000 meters altitude, transformers and switches require capacity reduction (approximately 1% per 100-meter elevation).
  • Product operating temperature does not reflect server environment.
Server liquid-cooled cabinet
Total heat dissipation capacity200kW
Server capacity42U server (maximum power ≤200 kW)
PDU400A*1
CDU
Rated heat exchange capacity200kW
Heat Exchange MethodLiquid-liquid plate heat exchanger
Secondary side flow rate20m³/h
Secondary side operating pressure0.25‑0.4Mpa
Secondary side operating pressure(1+1))Redundant variable-frequency centrifugal pump
Primary side flow rate20m³/h
Primary working pressure0.25‑0.4Mpa
Primary side water pumpSingle variable-frequency centrifugal pump
Control SystemSupports web-based remote monitoring, Modbus RTU/TCP, and SNMP protocols; features self-diagnosis of faults and alarm functionality.
Outdoor V-shaped dry cooler
Rated heat dissipation capacity200kW
Rated heat dissipation capacity2100mm*1100mm*1250mm
Structural styleV-shaped plate-fin structure
Fan950#*2psc
Supporting systemOptional spray atomization system