| Server liquid-cooled cabinet | |
|---|---|
| Total heat dissipation capacity | 200kW |
| Server capacity | 42U server (maximum power ≤200 kW) |
| PDU | 400A*1 |
| CDU | |
| Rated heat exchange capacity | 200kW |
| Heat Exchange Method | Liquid-liquid plate heat exchanger |
| Secondary side flow rate | 20m³/h |
| Secondary side operating pressure | 0.25‑0.4Mpa |
| Secondary side operating pressure | (1+1))Redundant variable-frequency centrifugal pump |
| Primary side flow rate | 20m³/h |
| Primary working pressure | 0.25‑0.4Mpa |
| Primary side water pump | Single variable-frequency centrifugal pump |
| Control System | Supports web-based remote monitoring, Modbus RTU/TCP, and SNMP protocols; features self-diagnosis of faults and alarm functionality. |
| Outdoor V-shaped dry cooler | |
| Rated heat dissipation capacity | 200kW |
| Rated heat dissipation capacity | 2100mm*1100mm*1250mm |
| Structural style | V-shaped plate-fin structure |
| Fan | 950#*2psc |
| Supporting system | Optional spray atomization system |
| *The full container of UL and CSA Certified needs to be customized separately. *These can be adapted to customer requirement. | |