| Subsystem | |
|---|---|
| Dimensions (L×W×H) | L×3600mm×2400mm,L≤10300m |
| Power per cabinet | ≤28 racks |
| Ground scaffold | 400mm |
| Power distribution system | N+1、2N |
| Access control | Integrated face recognition and fingerprint scanner – supports multiple authentication methods including face recognition, fingerprint scanning, password entry, and IC card authentication. |
| Flipped sunroof | Flipped glass skylight; supports fire safety linkage control |
| Smart Lighting | Energy-efficient LED lighting fixture with human motion sensor support |
| Cabinet | |
| Dimensions (W×H×D) | 600/800×2000/2200×1100/1200mm |
| Recommended Standard | IEC 60297‑1、GB/T 19520.1 |
| UPS | |
| Rated Capacity | 100kVA/kW、200kVA/kW、300kVA/kW、400kVA/kW |
| Module Power | 50kVA/kW |
| Rated Voltage | 220/230/240Vac |
| Rated Frequency | 50/60Hz |
| Topology | Dual Conversion Online |
| Battery cupboard | |
| 电池后备时间 | 15min,30min可选 |
| 智能温控 | 结合空调精密制冷,实现电池柜内部温控范围:20~30℃(可选) |
| 电池监控 | 根据实际UPS进行配置,支持监测每节蓄电池的内阻、电压、温度 |
| Liquid cooling system | |
| Liquid cooling system heat dissipation share | 60%~80% |
| Liquid cooling system heat dissipation rate | 100kW/200kW/300kW/400kW/800kW |
| Liquid cooling system medium | pure water |
| Liquid cooling system supply/return liquid temperature | Primary side: 35/45°C; Secondary side: 40/50°C |
| CDU dimensions(W×H×D) | 600×2000×1200mm (100kW、200kW、300kW)、800×2000×1200mm(400kW) |
| Air-cooling System | |
| Air-cooling System Architecture | Inter-row Air Conditioning 20%~40% |
| Air-cooled system cooling capacity | 12.5kW、25.5kW、35.5kW,43.5kW、51.5kW、62.5kW、65.5kW |
| Indoor unit dimensions (L×W×H) | 12.5kW、25.5kW、35.5kW(300×1200×2000),43.5kW、51.5kW、62.5kW、65.5kW(600×1200×2000) |