| Power Supply and Distribution | IT total load | 400kW | |
| Power density per cabinet | ≤150kW | |
| Power Supply Standard | Three‑phase four‑wire + PE, 380V / 400V / 415V AC, 50Hz/60Hz | |
| Power Distribution Unit (PDU) | 400A*2 | The intelligent PDU is optional. |
| battery capacity | 100kVA/100kW | |
| Battery standby time | 15 min | |
| Cabinet | IT cabinet capacity | 2 X 42U IT cabinet | |
| Cabinet dimensions (width x depth x height mm) | 600mm X 1200mm X 2000mm | |
| Temperature control | Net cooling capacity | 65.5kW per unit | |
| Temperature control range | 35~45 ℃ | |
| Cold and Hot Channels | Closed thermal channel | |
| Fire fighting | Automatic Fire Extinguishing System | A gas fire suppression system equipped with automatic temperature control, flue gas detection devices, and emergency release functionality | |
| Alarm | The monitoring system supports audio and visual alarms. | |
| fire extinguishing gas | Heptafluoropropane | |
| Early Detection | Support VESTA | |
| Monitor | Box door access control | Standard ID card access control | The IC card payment system is optional. |
| Cabinet access control | Standard mechanical door lock | The smart door lock is customizable. |
| Monitoring and Management | Internal temperature and humidity real‑time monitoring and control system, access control system, fire detection and control system | |
| Proximal display within the module | Remote access to the customer monitoring system display | |
| Mobile Operations and Maintenance | phone APP | The optional SMS Cat only supports remote display via the app; it does not support control. |
| Prefabricated Module Structure | External dimensions (length x width x height, mm) | 6058mm×3200mm×3200mm | |
| Insulation layer thickness | 50mm rock wool board | |
| Maintenance channel dimensions | Cold channel width: ≥1000 mm Hot channel width: ≥800 mm | |