• 浸没式算力单元

Immersive Computing Unit

Maintain vertical alignment (±1 degree) during installation. Operating environment: Temperature-20°C to 45°C, humidity ≤90% RH. Caution: Condensation may occur in low temperatures. For installations above 2,000 meters altitude, transformers and switches require capacity reduction (approximately 1% per 100-meter elevation). Product operating temperature does not reflect server environment.
  • Product Description
  • Product Specifications

Important Notes:

  • Maintain vertical alignment (±1 degree) during installation.
  • Operating environment: Temperature-20°C to 45°C, humidity ≤90% RH. Caution: Condensation may occur in low temperatures.
  • For installations above 2,000 meters altitude, transformers and switches require capacity reduction (approximately 1% per 100-meter elevation).
  • Product operating temperature does not reflect server environment.
42U horizontal immersion liquid-cooled cabinet
Total heat dissipation capacity100 kW
Server capacityStandard 42U cabinet can hold 21 units of 2U servers or 10 units of 4U servers.
Water pumpSingle variable-frequency centrifugal pump
Flow rate10m³/h
Working pressure0.25-0.4Mpa
Outdoor V-shaped dry cooler
Rated heat dissipation capacity100 kW
Overall dimensions2100mm*1100mm*1250mm
structural styleV-shaped plate-fin structure
Fan950#*2psc
supporting systemOptional spray atomization system
*The full container of UL and CSA Certified needs to be customized separately.