The container liquid cooling system is designed to continuously supply the heat-dissipation units of the internal high-hashrate servers with coolant meeting the required pressure, temperature, and flow conditions, ensuring a stable and favorable operating environment for the load.
The CADRO&DroLinBox HC45 V2 container liquid cooling system adopts forced-air cooling (dry cooler). Depending on the local ambient temperature, the internal cooling medium can be selected from antifreeze, deionized water, or pure water.

| Sub-component | Function | Main Components |
|---|---|---|
| Pump Station | Delivers and monitors the coolant status to maintain stable system operation | Centrifugal pump, expansion tank, sensors, valves, air vents, filters, piping, and other related accessories |
| Control Cabinet (including main control cabinet and fan control cabinet) | Controls the operation of all components in the pump station, reads sensor values and uploads them | Air circuit breakers, intermediate relays, PLC, switched-mode power supplies, touch screens, and other related accessories |
| Network & Power Distribution System | Provides networking and power distribution for the high-hashrate servers | Circuit breakers, aviation connectors, cables, network switches, and other related accessories |
| Water Distributor Assembly | Distributes and delivers the coolant flow | Manifolds, elbows, hoses, clamps, valves, and other related accessories |
| Container-Supplied Accessories | Supporting components and spare parts required for operating the container liquid cooling system | Screws, micro-switches, aviation plugs, hose clamps, rubber hoses, and related fittings |
| Dry Cooler | Transfers heat from the load to the atmosphere | Stainless steel heat-exchanger assembly, valves, pressure gauges, and other related accessories |
The pump station supplies two streams of coolant that meet the required temperature, pressure, flow, and medium specifications to the water distributor assembly. The distributor delivers the coolant to the server cold plates through two-stage distribution, and the cold plates carry away the heat generated inside the equipment. The heated coolant then enters the dry cooler, where forced-air convection driven by the power fans enables heat exchange between the air and the internal circulating medium. The cooled coolant is once again delivered by the pump station and distributor assembly back to the cold plates. This cycle repeats continuously, constantly removing the heat from inside the heat-generating load, keeping it in thermal equilibrium and maintaining a relatively stable internal temperature so that it always operates in an optimal environment.
The dry cooler uses water and air as cooling media. Inside the dry cooler, a series of parallel pipes carry the cooling water, with axial fans mounted on top. During operation, the heat of the flowing water inside the pipes is conducted through the pipe walls to the fins outside, which increase heat-transfer efficiency. The axial fans draw air from the top, enhancing air movement; the air flows between the fins and, through natural draft cooling or fan-forced ventilation, ensures effective contact between the air and the fins. Heat is transferred from the fins to the air, exchanging heat between the higher-temperature coolant coming from the cold plates and the low-temperature air, thereby cooling the liquid inside the pipes. After its temperature drops, the coolant is pumped back into the system by the pump set to dissipate heat once again.

| No. | Item | Specification | Remarks |
|---|---|---|---|
| Environmental Indicators | |||
| 1 | Operating Temperature | -35~40℃ | Outdoor |
| Operating Temperature | 5~40℃ | Indoor (adjustable fan control extends the controllable temperature range) | |
| 2 | Operating Humidity | 10%~90% | |
| 3 | Storage Temperature | -35~70℃ | |
| 4 | Storage Humidity | 5%~95% | |
| 5 | Altitude | ≤2000m | |
| Container Technical Specifications | |||
| 1 | External Dimensions (L×W×H) (mm) | 16154×2438×2896 | |
| 2 | High-Hashrate Server Capacity | 196 S21 Hyd. series and S19 Hyd. series high-hashrate servers | |
| 3 | Container Certification | China Classification Society certified | |
| 4 | Safety Certification | NFPA 79:2021 UL 508A:2018 R8.21 CSA C22.2 No. 14‑18 ANSI/ISO 12100:2012 | |
| 5 | Operating Power (kW) | 1047~1050 | Excluding dry cooler power consumption |
| 6 | Dry Cooler Power (kW) | 43.2 | |
| 7 | Input Voltage and Frequency | 400V±5% AC,60Hz/50Hz | |
| 8 | Transport Weight (t) | 19.5 | Excluding high-hashrate servers and coolant |
| 9 | Operating Weight (t) | 24 | Including high-hashrate servers and coolant |
| 10 | Main Switch Capacity of Distribution Cabinet (A) | 1200 | The container liquid cooling system includes two distribution cabinets, each with one 1200A main switch |
| 11 | Rated Current (A) | ≤986 | Rated current of each distribution cabinet in the container |
| 12 | Standard Power (kW) | 1047 | Excluding dry cooler power consumption |
| 13 | Maximum Power (kW) | 1050 | Excluding dry cooler power consumption |
| 14 | Rated Current per Server Slot (A) | ≤10 | The container liquid cooling system includes two distribution cabinets, each with one 1200A main switch |
| 15 | Internal Interface | DN125 (nominal size 139.7‑ISO 2852) | |
| 16 | Flow Rate (m³/h) | ≥85 | |
| Integrated Dry Cooler Technical Specifications | |||
| 1 | Type | Microchannel | |
| 2 | Heat Rejection Capacity (kW) | 1000 | |
| 3 | Outlet Water Temperature @30℃ Ambient | 35℃±1℃ | |
| 4 | Unit Certification | China Classification Society | |
| 5 | Safety Certification | NFPA 79:2021 UL 508A:2018 R8.21 CSA C22.2 No. 14‑18 ANSI/ISO 12100:2012 | |
| 6 | Operating Power (kW) | 20~32 | |
| 7 | Noise @25℃, 15m | 70dBA | |