The microchannel system is designed to continuously provide the cooling fluid with the required pressure, temperature and flow rate for the high computing power server cooling unit to ensure a good working environment for the load.
CD-HC7.5-V1, CD-HC8.5-V1 The microchannel system adopts forced air cooling (microchannel), and the internal cooling medium can be selected according to the local ambient temperature, suchasantifreeze, deionized water or pure water.

Table 3-1 Main components of the microchannel system
| Subcomponent | Component Features | Main components |
|---|---|---|
| Control cabinet | Control the start and stop of pumps and fans, and display the liquid supply temperature, pH value, and conductivity of the pipeline system | Circuit breakers, aviation plugs, switches, miniature circuit breakers, intermediate relays, PLCs, switching power supplies, touch screens, and other related accessories |
| Microchannel system | Transfer heat from the load to the atmosphere | Integrated water curtain, microchannel heat exchanger, fan, pump, manual exhaust valve, automatic exhaust valve, and other related accessories |
| Accessories Included with the Box | Microchannel system accessories and spare parts required for use | Screws, miniature switches, aviation plugs, clamps, rubber hoses, and related accessories |
Microchannel Working Principle: The microchannel system employs water and air as cooling media. Inside the microchannel, parallel pipes contain circulating cooling water, with an axial fan installed at the top. During operation, heat from the circulating water is conducted through the pipe walls to external fins, which enhance thermal efficiency. The axial fan draws air from the top to intensify airflow, allowing air to pass through the fins. Through natural convection or forced ventilation, the air effectively contacts the fins, transferring heat from the fins to the air. This facilitates heat exchange between the high-temperature coolant exiting the water-cooled plateandthe low-temperature air, achieving effective cooling of the liquid inside the pipes. The cooled coolant is then pumped back into the system for further heat dissipation.

| 40HC/8.5m Dry Tower‑V3 | |
|---|---|
| Overall dimensions | Transport dimensions: 12196mm × 2438mm × 2896mm Working dimensions: 8500mm × 2438mm × 2896mm |
| Total weight | 8500kg (8.5T) |
| Input voltage and frequency | 360‑440V AC 50/60Hz |
| Electrical standard | Core Electrical Components Passed UL Or CE Certified. |
| Control System | PLC, Touch Screen, pH & Conductivity Monitoring, Fan VFD & Alarms, Remote Monitoring, etc. |
| Heat transfer power | 1200kW@25℃ ambient temperature |
| Cooling medium | Pure/Soften/Distilled water +Corrosion Inhibitor+Antifreeze(as per requirements) |
| Dry cooler | Plate‑fin |
| Fan | 950#*12psc |
| Single unit air flow | 32000m³/h |
| Pipe | SS304 DN100 |
| Liquid supply temperature(℃) | 35℃ ±1℃ |
| Sound Pressure LpA (10 m/m) | ≤55 dB(A) |
| transportation standard | CCS |
| *The full container of UL and CSA Certified needs to be customized separately. *These can be adapted to customer requirement. | |