The container liquid-cooling system is designed to continuously supply the heat-dissipation units of the high-performance computing servers inside the container with coolant that meets the required pressure, temperature, and flow specifications, ensuring an optimal operating environment for the load.
The CADRO&DroLinBox HC40 V2 container liquid-cooling system adopts a forced-air cooling configuration (dry cooler); the internal cooling medium can be selected as appropriate antifreeze, deionized water, or pure water based on the local ambient temperature.
| Sub-assembly | Function | Main Components |
|---|---|---|
| Pump Station | Conveys and monitors the coolant status to maintain stable system operation | Centrifugal pump, expansion tank, sensors, valves, air vent valve, filter, piping, and other related accessories |
| Control Cabinet (includes main control cabinet and fan control cabinet) | Controls the operation of each component in the pump station, reads and displays the values from each sensor, and uploads them | Air switch, intermediate relay, PLC, switching power supply, touchscreen, and other related accessories |
| Network and Power Distribution System | Provides networking and power distribution for the high-performance computing servers | Electrical switches, aviation connectors, cables, network switches, and other related accessories |
| Water Distributor Assembly | Distributes and conveys the coolant flow | Manifold, elbows, hoses, clamps, valves, and other related accessories |
| On-board Accessories | The supporting components and spare parts required when operating the container liquid-cooling system | Screws, micro-switches, aviation plugs, hose clamps, rubber hoses, and related accessories |
| Dry Cooler | Transfers the heat from the load to the atmosphere | Stainless steel heat-exchanger assembly, valves, pressure gauges, and other related accessories |
The pump station supplies two streams of coolant that meet the requirements for temperature, pressure, flow, and medium to the water-distributor assembly. The distributor delivers the coolant to the server cold plates through a two-stage distribution process, and the cold plates carry away the heat generated inside the equipment. The warmed coolant then enters the dry cooler, where forced-air convection driven by the power fans enables heat exchange between the air and the internal circulating medium. The cooled coolant is again delivered through the pump station and the water-distributor assembly back to the cold plates. This cycle repeats continuously, persistently removing the heat from inside the heat-generating load, keeping it in a thermal equilibrium state and ensuring its internal temperature remains relatively stable and always operates in a favorable environment.
The dry cooler uses water and air as cooling media. Inside the dry cooler is a series of parallel pipes through which the cooling water flows, with axial fans mounted on top. During operation, the heat of the flowing water inside the pipes is conducted through the pipe walls to the fins outside the pipes; the fins increase the heat-transfer efficiency. The axial fans draw air from the top, enhancing air movement. Air flows through the spaces between the fins, and through either natural air cooling or fan-forced ventilation, ensures that the air can effectively contact the fins and that heat is transferred from the fins to the air. This exchanges heat between the higher-temperature coolant coming from the cold plates and the lower-temperature air, thereby cooling the liquid inside the pipes. After its temperature is lowered, the coolant re-enters the system via the pump set for further heat dissipation.

| No. | Item | Specification | Remarks |
|---|---|---|---|
| Environmental Indicators | |||
| 1 | Work Temperature | -35~40℃ | Outdoor |
| Work Temperature | 5~40℃ | Indoor (adjustable temperature range via fan control) | |
| 2 | Relative Humidity | 10%~90% | |
| 3 | Storage Temperature | -35~70℃ | |
| 4 | Storage Humidity | 5%~95% | |
| 5 | Altitude | ≤2000m | |
| Container Technical Indicators | |||
| 1 | Overall Dimensions (L×W×H) (mm) | 16154×2438×2896 | |
| 2 | High-Performance Server Capacity | 196 units of S21 Hyd. series and S19 Hyd. series high-performance servers | |
| 3 | Container Certification | China Classification Society (CCS) Certification | |
| 4 | Safety Certification | NFPA 79:2021 UL 508A:2018 R8.21 CSA C22.2 No.14‑18 ANSI/ISO 12100:2012 | |
| 5 | Operating Power (kW) | 1047~1050 | Excluding dry-cooler power consumption |
| 6 | Dry Cooler Power (kW) | 43.2 | |
| 7 | Input Voltage and Frequency | 400V±5% AC, 60Hz/50Hz | |
| 8 | Shipping Weight (T) | 19.5 | Excluding high-performance servers and coolant |
| 9 | Operating Weight (T) | 24 | Including high-performance servers and coolant |
| 10 | Main Switch Capacity of Power Distribution Cabinet (A) | 1200 | The container liquid-cooling system contains two power distribution cabinets, each with one 1200A main switch |
| 11 | Rated Current (A) | ≤986 | Rated current of each power distribution cabinet inside the container |
| 12 | Standard Power (kW) | 1047 | Excluding dry-cooler power consumption |
| 13 | Maximum Power (kW) | 1050 | Excluding dry-cooler power consumption |
| 14 | Rated Current per Server Slot (A) | ≤10 | The container liquid-cooling system contains two power distribution cabinets, each with one 1200A main switch |
| 15 | Internal Interface | DN125 (nominal size 139.7‑ISO 2852) | |
| 16 | Flow Rate (m³/h) | ≥85 | |
| Integrated Dry Cooler Technical Indicators | |||
| 1 | Type | Microchannel | |
| 2 | Heat Rejection Capacity (kW) | 1000 | |
| 3 | Outlet Water Temperature @30℃ Ambient | 35℃±1℃ | |
| 4 | Container Certification | China Classification Society (CCS) | |
| 5 | Safety Certification | NFPA 79:2021 UL 508A:2018 R8.21 CSA C22.2 No.14‑18 ANSI/ISO 12100:2012 | |
| 6 | Operating Power (kW) | 20~32 | |
| 7 | Noise @25℃, 15m | 70dBA | |